JL-8C/22-1反时限过流继电器又称为反时限电流继电器,作为继电保护元件主要用于发电机、变压器、输变电线路中,作为电力系统交流回路过负荷或短路的启动元件,给出报警信号或切除故障。JL-8C/22-1采用CMOS集成电路进行运算和比较,具有数码整定精度高、整定范围宽、整定方便、动作速度快、返回系数高、功耗低的特点。
型号 | 额定电流 | 整定范围 | 级差 | 返回系数 |
JL-8C/21-1 | 5A | 0.03A~0.49A | 0.01A | 0.9~0.97 |
JL-8C/21-2 | 5A | 0.1A~0.99A | 0.01A | 0.9~0.97 |
JL-8C/21-3 | 5A | 1.0A~5.0A | 0.1A | 0.9~0.97 |
JL-8C/21-4 | 5A | 2.0A~9.9A | 0.1A | 0.9~0.97 |
JL-8C/22-1 | 5A | 0.03A~0.49A | 0.01A | 0.9~0.97 |
JL-8C/22-2 | 5A | 0.1A~0.99A | 0.01A | 0.9~0.97 |
JL-8C/22-3 | 5A | 1.0A~5.0A | 0.1A | 0.9~0.97 |
JL-8C/22-4 | 5A | 2.0A~9.9A | 0.1A | 0.9~0.97 |
JL-8C/31-1 | 5A | 0.03A~0.49A | 0.01A | 0.9~0.97 |
JL-8C/31-2 | 5A | 0.1A~0.99A | 0.01A | 0.9~0.97 |
JL-8C/31-3 | 5A | 1.0A~5.0A | 0.1A | 0.9~0.97 |
JL-8C/31-4 | 5A | 2.0A~9.9A | 0.1A | 0.9~0.97 |
JL-8C/32-1 | 5A | 0.03A~0.49A | 0.01A | 0.9~0.97 |
JL-8C/32-2 | 5A | 0.1A~0.99A | 0.01A | 0.9~0.97 |
JL-8C/32-3 | 5A | 1.0A~5.0A | 0.1A | 0.9~0.97 |
JL-8C/32-4 | 5A | 2.0A~9.9A | 0.1A | 0.9~0.97 |
额定参数 | |
直流额定电压 | 110V、220V可选 |
交流额定电压 | 110V、220V可选 |
直流动作电压 | ≤70%额定电压 |
交流动作电压 | ≤75%额定电压 |
返回系数 | 0.9~0.97 |
整定范围 | 0.03~9.9A |
返回时间 | ≤27ms |
功耗 | ≤5W |
绝缘性能 | |
绝缘电阻 | 继电器外壳与外露带电端子之间用开路电压500V的兆欧表测量,绝缘电阻不小于10MΩ |
绝缘耐压 | 继电器外壳与外露带电端子之间能耐受2KV(有效值)50Hz试验电压,历时1分钟,无击穿或闪络现象 |
环境条件 | |
环境温度 | -15℃~55℃ |
工作电压 | 不大于120%额定电压 |
工作位置 | 任意 |
周围磁场强度 | 小于0.5mT |
环境相对湿度 | 不大于90% |
大气压力 | 80~110KPa |
极限温度 | -25℃~+70℃ |
海拔高度 | 不大于2500 米 |
凸出式固定安装结构